5-2 Digital Encoder Functional Block
The Digital Encoder Functional Block
The Digital Encoder functional block performs logic functions on four digital
input network variables to create a digital output network variable and a mode
output network variable. The following figure and tables summarize the inputs
and outputs of the Digital Encoder functional block:
Input Network Variables
Default name Default type Description
D1/D2/D3/D4
SNVT_switch
Four digital input network
variables which are processed by
the Digital Encoder.
Output Network Variables
Default name Default type Description
Digital_Out
SNVT_switch
The digital output network variable
determined by the Digital Encoder.
Mode_Out
SNVT_hvac_mode
(changeable)
The mode output network variable
determined by the Digital Encoder.
Configuring the Digital Encoder with the LonPoint
Plug-in
Right-click a Digital Encoder functional block and select Configure from the
shortcut menu to open the LonPoint Plug-in. The Digital Encoder window of the
LonPoint Plug-in contains the following tabs:
Digital Encoder, Lookup
Tables, Heartbeats, and Status.