Neuron Tools Errors Guide 77
NCC# Description
245
Network variable declaration not permitted if netvar_processing off [NCC#245]
Once the directive #pragma netvar_processing_off is encountered in a
program, network variable declarations are not permitted. This pragma
can only be used with the LonBuilder Microprocessor Interface Program
(MIP).
246
This I/O object type requires specification of a 'timeout' pin [NCC#246]
The I/O object being declared requires specification of an additional pin to
use as an external timeout signal. See the description of the I/O object
being declared in the
I/O Model Reference
for more information.
Seitenansicht 84