3-12 Network Cabling and Connections
155 47.2 22 22 22 22 22 22 20 20 18 16 16 14
165 50.3 22 22 22 22 22 22 20 18 18 16 16 14
Table 3.4 Power Cabling Requirements in AWG (continued)
Load (VA)
Feet
10 15 20 25 30 40 55 75 100 130 180 200
185 56.4 22 22 22 22 22 22 20 18 18 16 14 14
215 65.5 22 22 22 22 22 20 20 18 16 16 14 14
230 70.1 22 22 22 22 22 20 18 18 16 16 14 14
235 71.6 22 22 22 22 22 20 18 18 16 14 14 14
250 76.2 22 22 22 22 22 20 18 18 16 14 14 12
265 80.8 22 22 22 22 20 20 18 16 16 14 14 12
295 89.9 22 22 22 22 20 20 18 16 16 14 12 12
300 91.4 22 22 22 22 20 18 18 16 16 14 12 12
340
22 22 22 20 20 18 18 16 14 14 12 12
365
22 22 22 20 20 18 16 16 14 14 12 12
375
22 22 22 20 20 18 16 16 14 12 12 12
395
22 22 20 20 20 18 16 16 14 12 12
400
22 22 20 20 18 18 16 16 14 12 12
420
22 22 20 20 18 18 16 14 14 12 12
470
22 22 20 20 18 18 16 14 14 12
475
22 22 20 20 18 16 16 14 14 12
500
22 22 20 18 18 16 16 14 12 12
545
22 20 20 18 18 16 16 14 12 12
580
22 20 20 18 18 16 14 14 12 12
595
22 20 20 18 18 16 14 14 12
630
22 20 18 18 18 16 14 14 12
635
22 20 18 18 16 16 14 14 12
750
22 20 18 18 16 16 14 12 12
755
20 20 18 18 16 14 14 12 12
795
20 20 18 16 16 14 14 12
865
20 18 18 16 16 14 14 12
945
20 18 18 16 16 14 12 12
1000
20 18 16 16 16 14 12 12
1010
20 18 16 16 14 14 12 12
1190
20 18 16 16 14 14 12
1200
18 18 16 16 14 12 12
1260
18 18 16 14 14 12 12
1375
18 16 16 14 14 12 12
1500
18 16 16 14 14 12
1590
18 16 14 14 14 12
1645
18 16 14 14 12 12