Parameter PL-30
TP/RS485-
625
TP/RS485-
1250 TP/RS485-78
Network Bit Rate 1882 bps 625 kbps 1.25 Mbps 78 kbps
Alternate Rate N/A N/A N/A N/A
Wakeup Pin Direction Output N/A N/A N/A
XCVR Controls Preamble Yes N/A N/A N/A
General Purpose Data 00 8A 00 00
00 00 00
N/A N/A N/A
Allow Node Override Yes N/A N/A N/A
Receive Start Delay 1.0 bit 2.0 bits 2.0 bits 2.0 bits
Receive End Delay 10.4 bits 0.0 bits 0.0 bits 0.0 bits
Indeterminate Time 0.0 bits 4.0 bits 4.0 bits 4.0 bits
Min Interpacket Time 0.0 bits 0.0 bits 0.0 bits 0.0 bits
Turnaround Time N/A 0 µsec 0 µsec 0 µsec
Missed Preamble N/A 1.0 bit 1.0 bit 1.0 bit
Preamble Length 36.7 bits N/A N/A N/A
Use Raw Data No No No No
Table 26. Communications Parameters, Part 4
Parameter FO-10 DC-78 DC-625 DC-1250
Transceiver ID 24 (0x18) 27 (0x1B) 28 (0x1C) 29 (0x1D)
Media Fiber Optic Direct
Connect
Direct
Connect
Direct
Connect
Neuron Chip to
Transceiver Interface
Single Ended Differential Differential Differential
Interface Bit Rate 1.25 Mbps 78 kbps 625 kbps 1.25 Mbps
Input Clock 10 MHz 10 MHz 10 MHz 10 MHz
114 Communications Parameters for LONWORKS Routers