Seite 1 - Developer’s Guide

078-0507-01ADevelop BACnet applications using the FT 6000 EVKand the FT 6050 Smart Transceiver. IzoT BACnet Developer’s Guide

Seite 2 - Chips or LonPoint Modules

For example, in Figure 1 there is a nviSpaceTemp that is normally connected to some other nvo output from another device. If a BACnet Client is requ

Seite 3 - Contents

This is best understood by examining a LONWORKS nvi (in Figure 2), in particular nviSpaceTemp, based on the LONMARK VAV Functional Profile. In the VA

Seite 4 - Getting Started with BACnet

BACnet Interface Overview The following figure depicts the BACnet interface. FT 6000 Ba sed LonWorks DeviceLon Application( User Code)Lon Network V

Seite 5 - Hardware Requirements

BACnet messages that do affect the Network Variables are routed via the Mapping Functions, and then back to the LonTalk stack, where they are present

Seite 6

The modified or unmodified message is passed back to the LonTalk stack for further processing as normal at this point (3). Data Flow during a LO

Seite 7 - Using BACnet

BACnet Object to LONMARK SNVT Mapping – The “Mapping Table” 1. Network Variables The first issue is that SNVTs are “Structures” and BACnet objects

Seite 8 - BACnet Terminology

Device ID and Device Name The Object ID of the BACnet Device Object (“Device ID”) is required to be unique “Internetwork Wide”, as is the Object Name

Seite 9

Refer to the sample source code, in particular BACsimple.nc to see how this is used. 3. BAClon\mapping.nc a. This file contains the actual mapping

Seite 10 - Write Operation Resolution

Complex Mapping If a Network Variable has multiple fields, each field needs to be mapped to a separate BACnet Object. mapAnaToSNVT_hvac_overid__per

Seite 11

2. 3rd party BACnet Clients – of course, any BACnet Client, in theory, should be able to read all BACnet points served by the BACnet stack. 3.

Seite 12 - BACnet Interface Overview

Echelon, LON, LonWorks, Neuron, 3120, 3150, Digital Home, i.LON, FTXL, LonScanner, LonSupport, LNS, LonMaker, LonMark, LonPoint, LonTalk, NodeBuilder

Seite 14 - ONWORKS

Appendix A Glossary This appendix provides definitions for terms discussed in this manual. Using BACnet and LONWORKS with the FT 6000 EVK 21

Seite 15 - BACnet Object Properties

Application Device A LONWORKS device that runs an ISO/IEC 14908-1 application (OSI Layer 7). The application may run on a Neuron Chip or Smart T

Seite 16 - Mapping Table Structure

Configuration Properties (CPs) Configuration properties are data values that define the behavior of an application device by determining the manner i

Seite 17

Device A device that communicates on a LONWORKS network using CNP. A device may be an application device, network service device, or a router. Devi

Seite 18 - BACnet Test Tools

Functional Block Array A set of identical functional blocks. A functional block array is useful if your device contains two or more identical switch

Seite 19

OpenLNS Server Computer A computer running the OpenLNS Server software. The OpenLNS Server computer contains the OpenLNS global database, which incl

Seite 20 - 20 Using BACnet

Managed Network A network where a shared network management server, such as LNS, is used to perform network installation. Mandatory Network Variable/

Seite 21 - Glossary

Neuron Firmware A complete operating system including an implementation of the ISO/IEC 14908-1 protocol used by a Neuron Chip or Smart Transceiver.

Seite 22

Priority Array BACnet Outputs are never directly written to (*). A write is achieved by writing to the Present Value with a priority of 1 to 16. (Wit

Seite 23

Contents Getting Started with BACnet ... 4 Hardware Requirements ...

Seite 24

Service Button A push button or other actuator on a LONWORKS device that is used during installation to acquire the device’s Neuron ID. For a Neuron

Seite 25 - ONWORKS network

User-defined Functional Profile A non-standard functional profile defined by a device manufacturer. A user-defined functional profile should be used

Seite 27 - ONWORKS device applications

1 Getting Started with BACnet This chapter provides the information to get started with BACnet on the IzoT network. 4 Getting Started with BACnet

Seite 28

Hardware Requirements The following hardware is required to develop and test a BACnet application on the FT 6050 • IzoT Router – required to transla

Seite 29 - ONWORKS-IP Server

user to match the requirements of their site through most standard BACnet Workstations, including the BACnet Browser for IzoT. To do so, right click

Seite 30

2 Using BACnet This chapter explains the BACnet terminology and illustrates the differences between BACnet and LONWORKS. Using BACnet and LONWORK

Seite 31

BACnet Terminology The following terms are a brief summary of BACnet terminology. BACnet Network – A group of BACnet Devices on a single network, wh

Seite 32

Differences between BACnet and LONWORKS There is a fundamental difference between BACnet and LONWORKS “Input” and “Output” concepts pertaining to phy