Echelon OpenLNS Commissioning Tool Bedienungsanleitung Seite 359

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 393
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 358
OpenLNS CT User’s Guide 343
Synchronization Options
The Synchronization category contains the following options.
Automatic Update
Interval (Seconds)
Sets how frequently (in seconds) an OpenLNS CT client checks the
OpenLNS CT Event Log and updates its copy of an OpenLNS CT
drawing to incorporate any changes made by other clients. The
default automatic update interval is 10 seconds.
Set the interval to 0 to disable automatic updates. You can then
apply updates when you open a drawing, or you can manually apply
updates by clicking Add-ins, pointing to Synchronization, and then
clicking Apply Events.
Scope: Current network, current OpenLNS CT computer
Maximum Log Entries
per Drawing File
Sets the maximum number of entries to be stored in the OpenLNS
CT Event Log. Once the limit is reached, older entries will be
deleted to enable new entries to be logged. The default limit is 100
entries. To disable the event log, set the limit to 0.
Scope: Current network, all OpenLNS CT computers